WPD Turbine Water Meter - Hot
Whether for stand alone hot water metering or for use with the CF integrator as part of a complete Heat Metering System, Stream’s range of Turbine Hot Water Meters ensure a flowmeter for every application. From the standard ST/WEC - withstanding water to 130°C through the WP-QF for 200°C temperatures at pressures to 40Bar, to the WSD offering a vertical turbine for use in areas where straight pipe lengths may be difficult to achieve during installation.
- Patented hydrodynamically balanced rotor
- Patented symmetrical calibration adjustment
- Hermetically sealed register (IP68)
- Register may be rotated through 360 degrees
- High overload capacity
- Pattern approved removable measuring element
- Upto 3 pulsers (1xOD, 2x RD) may be fitted without breaking the approval seal
- Powder coating ensures maximum corrosion protection
| Performance data WP-Dynamic QH 130 ºC |
| Nominal Diameter |
DN |
40 |
50 |
65 |
80 |
| Size of meter (acc. to PTB-A22) |
Qn |
10 |
15 |
25 |
40 |
| Qmax |
maximum peak flow once lifetime 24 h Qmax or 5 min. 1.2 x Qmax |
m3/h |
20 |
30 |
60 |
90 |
| Qn |
continuous flow (±2%) |
m3/h |
10 |
15 |
25 |
45 |
| Qt |
transitional flow (±2%) |
m3/h |
1.8 |
1.8 |
2 |
3.2 |
| Qmin |
minimum flow (±5%) |
m3/h |
0.6 |
0.6 |
1 |
1.4 |
| |
starting flow |
m3/h |
0.3 |
0.3 |
0.3 |
0.35 |
| Nominal Diameter |
DN |
100 |
125 |
150 |
200 |
250 |
300 |
| Size of meter (acc. to PTB-A22) |
Qn |
60 |
100 |
150 |
250 |
400 |
600 |
| Qmax |
maximum peak flow once lifetime 24 h Qmax or 5 min. 1.2 x Qmax |
m3/h |
140 |
200 |
300 |
500 |
1000 |
1200 |
| Qn |
continuous flow (±2%) |
m3/h |
70 |
100 |
150 |
250 |
500 |
600 |
| Qt |
transitional flow (±2%) |
m3/h |
4.8 |
8 |
12 |
20 |
45 |
50 |
| Qmin |
minimum flow (±5%) |
m3/h |
2 |
3.5 |
4.5 |
8 |
20 |
25 |
| |
starting flow |
m3/h |
0.6 |
1.1 |
1.7 |
2 |
10 |
15 |
View more information on our WPD RD pulse units...