WSD High PressureTurbine Flowmeter

 WSD High PressureTurbine Flowmeter

Download Data Sheet

40 Bar Pressure Rated Flow Sensor for hot water up to 130 ºC DN 50 ... DN 150
  • Measuring range better than metrological class C
  • Pressure rated 40 Bar
  • Hermetically sealed register (IP 68)
  • Interchangeable measuring element
  • High overload capability
  • Up to 3 pulsers (1 x OD, 2 x RD) may be fitted without breaking the approval seal
  • Register may be rotated through 360º
  • Powder coating ensures maximum corrosion protection
  • Not affected by external magnetic fields
  • Can be used as flow sensor for heat meters

Nominal Diameter 

DN 

50

65

80

100

150

 

Size of meter (acc. to PTB-A22) 

Qn 

15

25

40

60

150

 

Maximum peak flow (few minutes) +/-2% 

Qmax 

m3/h 

30

60

85

125

300

Continuous flow +/-2% 

Qn 

m3/h 

15

25

40

60

150

Transitional flow ±2% 

Qt 

m3/h 

1.5

2.5

2.5

4

12

Minimum flow ±5% 

Qmin 

m3/h 

0.25

0.3

0.3

0.5

0.8

Starting flow 

m3/h 

0.1

0.07

0.1

0.15

0.5